Silicone Braced Line Post
Silicone Line Post Insulator is one kind of power line hardware.
It is used in power line transmission and distribution system.
Material: Silicone
High mechanical capabilities
Other types of insulator include Suspension insulators, Pin insulators, Strain Insulators, Stay Insulators, Spool insulators, Porcelain Insulators.
Product Details
General
| Application | Braced Line Post |
| Fitting – Ground End | Aluminum Flat |
| Fitting – Live Line End | Two Hole Blade |
| Material | Silicone |
| Material – End Fitting | Galvanized Steel |
| Shed Style | Uniform |
| Strength Rating – Minimum Ultimate, Longitudinal (L) | 1550 lb (703.07 kg) |
| Strength Rating – Minimum Ultimate, Vertical (V) | 113500 lb (57182.73 kg) |
| Tensile Strength | 7500 lb (3401.94 kg) |
| Type | Braced Line Post |
Dimensions
| Angle | 12 |
| Diameter – Shed(s) | 5.06 in (128.52 mm) |
| Distance From Pole | 2 in (50.8 mm) |
| Height | 82 in (2082.8 mm) |
| Length | 12 in (304.8 mm) |
| Length – Brace Section | 87 in (2209.8 mm) |
| Length – Effective | 58.2 in (1478.28 mm) |
| Length – Suspension Insulator | 80.3 in (2039.62 mm) |
| Rod Diameter | 2.5 in (63.5 mm) |
| Width | 10 in (254 mm) |
Electrical Ratings
| Arc Distance – Dry | 46.7 |
| Creep and Leakage Distance | 120 |
| Critical Impulse Flashover (CIFO) – Negative | 820 |
| Critical Impulse Flashover (CIFO) – Positive | 710 |
| Flashover Voltage – 60 Hz Dry | 460 kV |
| Flashover Voltage – 60 Hz Wet | 415 kV |
| Voltage Rating | 115/138 V |
| Withstand Voltage – 60 Hz Dry | 460 |
| Withstand Voltage – 60 Hz Wet | 310 kV |
| Withstand Voltage – Lightning Impulse (Negative) | 735 kV |
| Withstand Voltage – Lightning Impulse (Positive) | 635 kV |
Certifications and Compliance
| Industry Standard(s) | ANSI |
Resources and Downloads
| Specifications | Download PDF |
| Technical Drawings | Download PDF |