Select Page

PDI-35 Deadend, Silicone Polymer, 2.94 lb

Silicon polymer Clevis Tongue

  • 35kV Deadend Insulator
  • PDI-35 available with other ANSI and IEC end fittings.

Product Details

General

ApplicationDeadend
Cantilever Bending Strength – Routine7500
Construction Material – MainSilicone Polymer
Fitting – Ground/BaseClevis
Fitting – Live Line EndTongue
Insulator TypeN/A
MaterialSilicone Polymer
Material – End FittingSteel
Material – Pin (Cotter)Stainless Steel
Number of Sheds8
Shed StyleUniform
Strength Rating – Ultimate15000 lb / 6808.8 kg
Tensile Strength15 K
Tensile Strength – Routine7500
TypePDI-35

Dimensions

Diameter – Shed(s)3
Length – Effective25.0 in / 635 mm
Rod Diameter0.625
Thickness – Housing0.148
Weight2.94 lb / 1.335 kg

Electrical Ratings

Arc Distance – Dry20
Creep and Leakage Distance33 IN (838 mm)
Critical Impulse Flashover (CIFO) – Negative360
Critical Impulse Flashover (CIFO) – Positive325
Flashover Voltage – 60 Hz Dry200
Flashover Voltage – 60 Hz Wet160
Voltage – Line35000 V
Withstand Voltage – 60 Hz Dry170
Withstand Voltage – 60 Hz Wet130

Logistics

Pallet Quantity300
Standard Package15

Resources and Downloads

SpecificationsDownload PDF
Technical DrawingsDownload PDF