Select Page

Line Post Insulators

Line Post Insulator is one kind of power line hardware used in power line transmission and distribution system.
Other types of insulator include Suspension insulators, Pin insulators, Strain Insulators, Stay Insulators, Spool insulators, Porcelain Insulators.

Product Details

General

Cantilever Bending Strength – Max.6180 lb
Cantilever Bending Strength – Routine3090 lb
Fitting – Ground/BaseRigid Gain Base
Fitting – Live Line EndTear Drop Blade
MaterialSilicone Rubber
Number of Sheds10

Dimensions

Diameter – Large Shed10.08 in (256.03 mm)
Diameter – Small Shed6.96 in (176.78 mm)
Length – Effective29.4 in (746.76 mm)
Rod Diameter2.5 in (63.5 mm)
Weight50 lb (22.68 kg)

Electrical Ratings

Arc Distance – Dry23.1 in (587 mm)
Creep and Leakage Distance60 in (1524mm)
Critical Impulse Flashover (CIFO) – Negative470 kV
Critical Impulse Flashover (CIFO) – Positive360 kV
Flashover Voltage – 60 Hz Dry230 kV
Flashover Voltage – 60 Hz Wet180 kV
Voltage Rating69 kV

Resources and Downloads

SpecificationsDownload PDF
Technical DrawingsDownload PDF