Select Page

Horizontal Line Post

Horizontal Line Post Insulator is one kind of power line hardware.
It is used in power line transmission and distribution system.
Industry Standard(s) ANSI
Other types of insulator include Suspension insulators, Pin insulators, Strain Insulators, Stay Insulators, Spool insulators, Porcelain Insulators
Weathersheds molded with proprietary silicone rubber

Product Details

General

ApplicationHorizontal Line Post
Cantilever Bending Strength – Max.2800 Lbs (12.5 kN)
Cantilever Bending Strength – Routine1235 Lbs. (5.5 kN)
EU RoHS IndicatorContact Manufacturer
Fitting – Ground/BaseGain Base
Fitting – Live Line EndHorizontal Clamptop
MaterialSilicone
Material – End FittingGalvanized Steel
Number of Sheds2
Tension Range2500 lb (1133.98 kg)

Dimensions

Angle5
Diameter – Shed(s)4.8 in (121.92 mm)
Length – Effective12.5 in (317.5 mm)
Rod Diameter1.5 in (38.5 mm)
Thickness – Housing0.22 in (5.59 mm)
Weight9.8 lb (4.45 kg)

Electrical Ratings

Arc Distance – Dry7.4 in (188mm)
Creep and Leakage Distance11 in (279mm)
Critical Impulse Flashover (CIFO) – Positive150 kV
Flashover Voltage – 60 Hz Dry90 kV
Flashover Voltage – 60 Hz Wet70 kV
Voltage – Line15000 V
Voltage Rating15 kV
Withstand Voltage – Lightning Impulse (Positive)140 kV

Logistics

Carton Quantity2
Pallet Quantity40
Standard Package3

Resources and Downloads

SpecificationsDownload PDF
Technical DrawingsDownload PDF