Product Details
General
Application | Suspension |
Fitting – Ground/Base | Y-Clevis |
Fitting – Live Line End | Ball |
Material – End Fitting | Steel |
Number of Sheds | 72 |
Shed Style | Uniform |
Strength Rating – Ultimate | 25000 lb (11339.81 kg) |
Tensile Strength | 111 kN |
Tensile Strength – Routine | 12500 lb (5669.9 kg) |
Dimensions
Diameter – Shed(s) | 3.7 in (93.98 mm) |
Length – Effective | 120.1 in (3050.54 mm) |
Rod Diameter | 0.625 in (15.88 mm) |
Thickness – Housing | 0.12 (3.05 mm) |
Weight | 15.9 lb (7.21 kg) |
Electrical Ratings
Arc Distance – Dry | 110” (2794 mm) |
Creep and Leakage Distance | 275 IN (6985 mm) |
Critical Impulse Flashover (CIFO) – Negative | 1740 kV |
Critical Impulse Flashover (CIFO) – Positive | 1705 kV |
Flashover Voltage – 60 Hz Dry | 990 kV |
Flashover Voltage – 60 Hz Wet | 920 kV |
Voltage – Line | 330000 V |
Logistics
Standard Package | 1 |
Resources and Downloads
Specifications | Download PDF |
Technical Drawings | N/A |