Select Page

Silicone Station Post Insulator

Silicone Station Post Insulator is one kind of power line hardware.
It is used for taking care of hardware at power plants and substations support electric links.
It possesses strong cast cycloaliphatic epoxy compound for suitable strength.
It can also safeguard and stabilize scattering of power force delivered at power plants.

Product Details

General

ApplicationStation Post
Cantilever Bending Strength – Routine1517
Fitting – Ground/Base5″ B.C. Tapped
Fitting – Live Line End5″ B.C. Tapped
MaterialSilicone
Material – End FittingGalvanized Steel
Number of Sheds31
Shed StyleAlternating
Tensile StrengthStandard Strength
Tensile Strength – Routine30000 lb
Torsional Strength9000

Dimensions

Diameter – Large Shed7.3
Diameter – Small Shed6.1
Length – Effective54 in (1371.6 mm)
Rod Diameter2.5
Weight51 lb (23.13 kg)

Electrical Ratings

BIL650 kV
Creep and Leakage Distance145 in (3700 mm)
Voltage – Line138 kV
Withstand Voltage – 60 Hz Wet280
kV Class138 kV

Certifications and Compliance

Industry Standard(s)ANSI TR 288

Resources and Downloads

SpecificationsDownload PDF
Technical DrawingsDownload PDF