Product Details
General
Cantilever Bending Strength – Max. | 2140 LB |
Cantilever Bending Strength – Routine | 1070 LB |
Fitting – Ground End | Al. Gain |
Fitting – Live Line End | Clamptop |
Number of Sheds | 26 |
Shed Style | Uniform |
Dimensions
Angle | 12 ° |
Diameter – Shed(s) | 7.6 IN (193 mm) |
Length | 14 in |
Length – Effective | 81 in |
Rod Diameter | 2.5 |
Thickness – Housing | 0.12 in |
Width | 8.06 in |
Electrical Ratings
Arc Distance – Dry | 71 IN (1739.5 mm) |
Creep and Leakage Distance | 180 IN (4572 mm) |
Critical Impulse Flashover (CIFO) – Negative | 1195 kV |
Critical Impulse Flashover (CIFO) – Positive | 1095 kV |
Flashover Voltage – 60 Hz Dry | 700 kV |
Flashover Voltage – 60 Hz Wet | 600 kV |
kV Class | 230.00 kV |
Resources and Downloads
Specifications | Download PDF |
Technical Drawings | N/A |