Product Details
General
| Application | Station Post |
| Cantilever Bending Strength – Routine | 2203 lb |
| Fitting – Ground/Base | 5″ BOLT CIRCLE |
| Fitting – Live Line End | 5″ BOLT CIRCLE |
| Material | Porcelain |
| Material – End Fitting | Galvanized Steel |
| Number of Sheds | 28 |
| Tensile Strength | High Strength |
| Tension Range | 24998 lb |
| Torsional Strength | 90012 in-lbs. (10170 N-m) |
Dimensions
| Diameter – Shed(s) | 8.27″ (210 mm) |
| Height | 54 in (1371.6 mm) |
| Weight | 169.3 lb (76.79 kg) |
Electrical Ratings
| BIL | 650 kV |
| Creep and Leakage Distance | 116″ (2947 mm) |
| Critical Impulse Flashover (CIFO) – Negative | 900 kV |
| Critical Impulse Flashover (CIFO) – Positive | 710 kV |
| Flashover Voltage – 60 Hz Dry | 435 kV |
| Flashover Voltage – 60 Hz Wet | 335 kV |
| Voltage Application | 138 kV |
| Withstand Voltage – 60 Hz Wet | 275 kV |
Certifications and Compliance
| Industry Standard(s) | ANSI C29.9 |
Resources and Downloads