Product Details
General
Application | Station Post |
Cantilever Bending Strength – Routine | 2203 lb |
Fitting – Ground/Base | 5″ BOLT CIRCLE |
Fitting – Live Line End | 5″ BOLT CIRCLE |
Material | Porcelain |
Material – End Fitting | Galvanized Steel |
Number of Sheds | 28 |
Tensile Strength | High Strength |
Tension Range | 24998 lb |
Torsional Strength | 90012 in-lbs. (10170 N-m) |
Dimensions
Diameter – Shed(s) | 8.27″ (210 mm) |
Height | 54 in (1371.6 mm) |
Weight | 169.3 lb (76.79 kg) |
Electrical Ratings
BIL | 650 kV |
Creep and Leakage Distance | 116″ (2947 mm) |
Critical Impulse Flashover (CIFO) – Negative | 900 kV |
Critical Impulse Flashover (CIFO) – Positive | 710 kV |
Flashover Voltage – 60 Hz Dry | 435 kV |
Flashover Voltage – 60 Hz Wet | 335 kV |
Voltage Application | 138 kV |
Withstand Voltage – 60 Hz Wet | 275 kV |
Certifications and Compliance
Industry Standard(s) | ANSI C29.9 |
Resources and Downloads
Specifications | Download PDF |
Technical Drawings | Download PDF |