Select Page

Line Post Insulator, Cantilever Bending Strength – Max: 1540 LB

Line Post Insulator is one kind of power line hardware used in power line transmission and distribution system.
Other types of insulator include Suspension insulators, Pin insulators, Strain Insulators, Stay Insulators, Spool insulators, Porcelain Insulators.

Product Details

General

Cantilever Bending Strength – Max.1540 LB
Cantilever Bending Strength – Routine770 LB
Fitting – Ground EndSteel Gain
Fitting – Live Line EndLong Tear Drop Blade
Number of Sheds80
Shed StyleUniform

Dimensions

Diameter – Shed(s)5.06
Length – Effective107.9 in (2740.66 mm)
Rod Diameter2.500 in (63.5 mm)
Thickness – Housing> 3MM

Electrical Ratings

Arc Distance – Dry97.6 IN (2479 MM)
Creep and Leakage Distance252 IN (6401 MM)
Critical Impulse Flashover (CIFO) – Negative1605
Critical Impulse Flashover (CIFO) – Positive1515
Flashover Voltage – 60 Hz Dry955
Flashover Voltage – 60 Hz Wet790
kV Class345.00 kV

Resources and Downloads

SpecificationsDownload PDF
Technical DrawingsN/A