Select Page

Line Post Insulator, 69 KV Voltage Rating

Line Post Insulator
Diameter Range 6.96 in – 10.08 in
Votage Rating 69 kv

Product Details

General

Cantilever Bending Strength – Max.5000 lb (2267.96 kg)
Cantilever Bending Strength – Routine2500 lb (1133.98 kg)
Fitting – Ground/BaseRigid Gain Base
Fitting – Live Line EndTear Drop Blade
MaterialSilicone Rubber
Number of Sheds10

Dimensions

Diameter – Large Shed10.08 in (256.03 mm)
Diameter – Small Shed6.96 in (6.96 mm)
Length – Effective29.9 in (759.46 mm)
Rod Diameter2.5 in (63.5 mm)
Weight50 lb (22.68 kg)

Logistics

Arc Distance – Dry23.1 in (587 mm)
Creep and Leakage Distance60 in (1524mm)
Critical Impulse Flashover (CIFO) – Negative470 kV
Critical Impulse Flashover (CIFO) – Positive360 kV
Flashover Voltage – 60 Hz Dry230 kV
Flashover Voltage – 60 Hz Wet180 kV
Voltage Rating69 kV

Resources and Downloads

SpecificationsDownload PDF
Technical DrawingsDownload PDF