Product Details
General
Cantilever Bending Strength – Max. | 2500 LB / 11348.8 kg |
Cantilever Bending Strength – Routine | 1250 LB / 567.4 kg |
Fitting – Ground End | Al. Gain |
Fitting – Live Line End | Clamptop |
Material | Cilicone polymer |
Number of Sheds | 22 |
Shed Style | Uniform |
Dimensions
Angle | 12 ° |
Diameter – Shed(s) | 7.6 IN (193 mm) |
Length | 14in / 356 mm |
Length – Effective | 70 in / 178 mm |
Rod Diameter | 2.5 |
Thickness – Housing | 0.12 in / 3 mm |
Width | 8.06 in / 205 mm |
Electrical Ratings
Arc Distance – Dry | 60 IN (1470 mm) |
Creep and Leakage Distance | 152 IN (3861 mm) |
Critical Impulse Flashover (CIFO) – Negative | 1035 kV |
Critical Impulse Flashover (CIFO) – Positive | 930 kV |
Flashover Voltage – 60 Hz Dry | 600 kV |
Flashover Voltage – 60 Hz Wet | 520 kV |
kV Class | 161.00 kV |
Resources and Downloads
Specifications | HLHLPI001.PDF |
Technical Drawings | HLHLPI001 Drawings.PDF |