Select Page

Distribution Arrester, 10.2 KV MCOV

Distribution arresters are protective devices installed on overhead distribution networks to safeguard electrical equipment and conductors from transient overvoltages, primarily caused by lightning strikes and switching surges. They function by diverting excess surge energy safely to the ground, thereby maintaining system insulation integrity and preventing equipment failure in medium-voltage power line infrastructure.

Engineered for utility-grade reliability, these arresters are commonly deployed on pole-mounted transformers, line taps, and distribution feeders to enhance system resilience and reduce outage frequency.

Key Features:

  • High-energy surge protection for overhead distribution systems
  • Fast-response nonlinear metal oxide varistor (MOV) technology
  • Robust polymer or porcelain housing for environmental resistance
  • High insulation coordination with distribution voltage classes
  • Corrosion-resistant hardware suitable for outdoor installations
  • Designed for repetitive surge handling without performance degradation
  • Compatible with IEC/IEEE standards for utility applications
  • UV-resistant construction for extended service life in harsh climates
  • Easy pole-mount installation with minimal maintenance requirements
  • Effective protection for transformers, conductors, and switchgear

Product Details

General

ApplicationDistribution
Bracket TypeNone
ColorGray
MaterialSilicone Polymer Housing
Mounting PositionUpright
Type5 kA

Dimensions

Stud TypeM12

Electrical Ratings

Creep and Leakage Distance390 mm
Current – Low Current Long Duration (LCLD) Test75
Duty Cycle12 kV
Frequency Rating48-62 Hz
MCOV10.2 kV
Maximum .5 Microsecond Discharge Volts @ Classifying Current40.0 kV
Maximum Discharge Voltage32.9 kV @ 1.5 kA
35.6 kV @ 3 kA
36.9 kV @ 5 kA
40.6 kV @ 10 kA
46.1 kV @ 20 kA
54.7 kV @ 40 kA
Maximum Switching Surge Protective Level @ 500A27.8 kV
Minimum Strike155.0 mm
Pressure Relief Capability-Symmetrical rms (kA)15
Time – Low Current Long Duration (LCLD) Test2000 µs
Withstand Voltage – 60 Hz Wet34
Withstand Voltage – Lightning Impulse125
Withstand Voltage – Switching Impulse31.3

Resources and Downloads

SpecificationsDownload PDF
Technical DrawingsN/A