Select Page

Line Surge Arrester, 34.5 KV Line Voltage

Line Surge Arrester
Custom designs available up to 765 kV
Detailed spcification in PDF

Product Details

General

Application35 kV and Below
TypeLine Arresters

Electrical Ratings

Creep and Leakage Distance39.6 in (1005.8 mm)
Duty Cycle27 kV
Frequency Rating48-62 Hz
MCOV22 kV
Maximum .5 Microsecond Discharge Volts @ Classifying Current91.8 kV
Maximum Discharge Voltage68.7 kV @ 1.5 kA
73.3 kV @ 3 kA
77.7 kV @ 5 kA
85.4 kV @ 10 kA
96.1 kV @ 20 kA
114.3 kV @ 40 kA
Maximum Switching Surge Protective Level @ 500A65.9 kV
Pressure Relief Capability-Symmetrical rms (kA)20
Voltage – Line34.5 kV

Certifications and Compliance

Industry Standard(s)IEEE/IEC

Resources and Downloads

SpecificationsDownload PDF
Technical DrawingsDownload PDF