10.2 kV MCOV Distribution Arrester

Distribution arresters are critical surge protection devices used in power line construction to safeguard electrical equipment from overvoltage transients caused by lightning strikes or switching operations. Installed on distribution systems (typically 1–38 kV), these arresters divert excess energy safely to the ground, ensuring system reliability and extending equipment life.

Key Features:

  • High Energy Absorption: Utilizes zinc oxide (ZnO) varistor blocks for superior surge handling capacity.
  • Weather-Resistant Housing: UV-resistant polymer or porcelain insulation ensures long-term durability in harsh environments.
  • Compact and Lightweight Design: Simplifies installation and maintenance on poles and substations.
  • Creepage and Leakage Control: Optimized shed profiles reduce surface current paths in polluted or wet conditions.
  • Fail-Safe Mechanism: Designed to disconnect from the line in the event of internal failure to maintain system safety.
  • Standard Compliance: Meets or exceeds ANSI/IEEE C62.11 and IEC 60099-4 standards.

Product Details

General

ApplicationDistribution
Cantilever Bending Strength – Max.135 Nm
ColorGray
EU RoHS IndicatorContact Manufacturer
MaterialSilicone Polymer Housing
Mounting PositionUpright
TypeDistribution

Dimensions

Height9.4 in (238.76 mm)
Minimum Mounting Spacing on Center (Sea Level) – Phase to Ground5.3 in (134.62 mm)
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase7.3 in (185.42 mm)
Stud Type3/8-16

Electrical Ratings

Creep and Leakage Distance15.4 in (391 mm)
Current – Low Current Long Duration (LCLD) Test250 A
Duty Cycle12 kV
Frequency Rating48-62 Hz
MCOV10.2 kV
Maximum .5 Microsecond Discharge Volts @ Classifying Current36.2 kV
Maximum Discharge Voltage27.8 kV @ 1.5 kA
29 kV @ 3 kA
30.2 kV @ 5 kA
32.5 kV @ 10 kA
35.9 kV @ 20 kA
41.6 kV @ 40 kA
Maximum Switching Surge Protective Level @ 500A23.9 kV
Minimum Strike6.1 in (154.94 mm)
Pressure Relief Capability-Symmetrical rms (kA)20
Time – Low Current Long Duration (LCLD) Test2000 µs
Withstand Voltage – 60 Hz Wet26.9
Withstand Voltage – Lightning Impulse60.1