10.2 kV MCOV Distribution Arrester
10.2 kV MCOV Distribution Arrester–Surge Arrester
Silicone Polymer Housing with vertical and perpendicular mounting position
Riser pole
Color: Gray
It aims to prevent power cords grounds faults and shorts caused by lighting or switching overvoltages.
Protect nearby animal and passersby
Product Details
General
Application | Distribution |
---|---|
Cantilever Bending Strength – Max. | 135 Nm |
Color | Gray |
EU RoHS Indicator | Contact Manufacturer |
Material | Silicone Polymer Housing |
Mounting Position | Upright |
Type | Distribution |
Dimensions
Height | 9.4 in (238.76 mm) |
---|---|
Minimum Mounting Spacing on Center (Sea Level) – Phase to Ground | 5.3 in (134.62 mm) |
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase | 7.3 in (185.42 mm) |
Stud Type | 3/8-16 |
Electrical Ratings
Creep and Leakage Distance | 15.4 in (391 mm) |
---|---|
Current – Low Current Long Duration (LCLD) Test | 250 A |
Duty Cycle | 12 kV |
Frequency Rating | 48-62 Hz |
MCOV | 10.2 kV |
Maximum .5 Microsecond Discharge Volts @ Classifying Current | 36.2 kV |
Maximum Discharge Voltage | 27.8 kV @ 1.5 kA 29 kV @ 3 kA 30.2 kV @ 5 kA 32.5 kV @ 10 kA 35.9 kV @ 20 kA 41.6 kV @ 40 kA |
Maximum Switching Surge Protective Level @ 500A | 23.9 kV |
Minimum Strike | 6.1 in (154.94 mm) |
Pressure Relief Capability-Symmetrical rms (kA) | 20 |
Time – Low Current Long Duration (LCLD) Test | 2000 µs |
Withstand Voltage – 60 Hz Wet | 26.9 |
Withstand Voltage – Lightning Impulse | 60.1 |
Logistics
Pallet Quantity | 192 |
Resources and Downloads
Specifications | Download PDF |